1. Home  |  Sitemap  |  Contact Us     
        E Series Vector frequency Inverter
         Product Description :

        E-Series Frequency Inverter

        Technical Specification of E180 Series

        1. “High precision”, “high performance”, “high cost-effective”.
        To satisfy the increasingly higher requirements on the industrial production of frequency inverters, Hangzhou Delixi develops a new E series frequency inverter aiming at the market demands. Compared with the old frequency inverters, its precision and performance are improved substantially besides its optimized structure and appearance. Its powerful built-in function may better fulfill the needs of different industries.
        2. High control precision
        Speed regulation scope
        1:100 (SVC) 1:1000(VC)
        Speed stabilizing scope
        0.5%(SVC) 0.02%(VC)
        Torque control precision
        5% (VC)

        3.Rapid torque response

        SVC: Torque response < 20ms

        VC: Torque response < 5ms
        4.High starting torque
        SVC: 0.5 Hz may provide 150% starting torque
        VC: 0 HZ may provide 180% torque at zero speed
        5.Various vector controls of motors are available
        E180 Series may drive asynchronous motor and synchronous motor.
        6.Diversified menu display modes
        7.Function of built-in timer
        It has two built-in timers to collect input timing signals and realize the output of timing signals. Such function may be used separately or in any combination.
        8.Built-in virtual time-delay relay
        It has 5 built-in virtual time-delay relays to conduct simple logic operation for multi-functional output terminals and digital input terminal signals. The logic result may be considered as equivalent to input terminal function and also may be output from the multi-functional output terminals. Moreover, the logic results may be conducted with time-delay and negation operations.
        9.Function of built-in operating module
        One quad operating module is built in. such module may conduct simple addition, subtraction, multiplication, division, judgment of size and integral operations. Each operation has 4 input directing addresses and one output directing address. The input directing address is function code.
        10.Function of rapid current limiter
        In the case the current exceeds the current protection point, the rapid current limiter may keep the current within the current protection point to prevent frequently sending over-current alarm by the frequency inverter and protect the equipment.
        11.Excellent capability of power drive control
        The maximum drive capability of 24V output power of E-series frequency inverter, equipped with current limiting alarm function, may be 300mA.
        The user may use it to supply power to text, touch screen, PLC and relay instead of connecting to an external switch.
         

        Technical specification of E-Series Frequency inverter

         

        Item

        Specifications

        Control

        Control method

        V/F control

        Vector control SVC

        Vector control VC    Invalid for E100/E102 series

        Frequency accuracy

        Digital value 0.02%

        Analogue value 0.1%

        V/F curve

        Linear   Square root  Any V/F

        Overload capacity

        G type machine: 150% rated current 60s; 180% rated current 3s

        P type machine: 120% rated current 60s;  150% rated current 3s

        Starting torque

        G type machine: 0.5Hz/150% SVC; 0Hz/180% VC

        Speed regulation scope

        1:100 SVC

        1:1000 SVC

        Speed stabilizing scope

        0.5% SVC

        0.02%

        Torque control precision

        5% VC

        Torque compensation

        Manual torque compensation 0.10% 30.0% Automatic torque compensation

        Operation mode

        Keyboard, terminal, RS 485 communication

        Functions of basic type

        Frequency source

        14 types of main frequency sources, 14 types of auxiliary frequency sources. Combined switching-over in multiple ways are available. Diversified input method of frequency source, keyboard potentiometer, external analog quantity, digital set point, pulse frequency, multi-speed, simple PLC, communication, operation results.

        Torque source

        14 types of torque source, including digital set point, external analog quantity, pulse set point, multi-stage instructions, communication, operation results.

        Time of ACC/DEC

        4 groups of straight lines, switchable by means of time of ACC/DEC, S curve 1, S curve 2

        Emergency shut down

        Stop the output of the frequency inverter suddenly

        Multi-speed

        It may set 16 speeds maximally, which may be switched by means of multi instruction terminals.

        Simple PLC function

        It may set 16 speeds, and the deceleration time, operation time and frequency source may be set independently.

        Jogging control

        The jogging frequency and jogging time of ACC/DEC may be set independently, and it may also set the preference to jogging under operation status.

        Speed tracking

        The load speed tracked by the frequency inverter is started.

        Fixed-length, fixed-distance control

        It may realize the fixed-length and fixed-distance control by the pulse input.

        Counting control

        It may realize the counting function by the pulse input.

        Swinging control

        It may be applied for the winding equipment of textiles.

        Built-in PID

        It may realize SVC.

        AVR function

        It may ensure the output of constancy in voltage fluctuation of network.

        DC brake

        It may stop the machine steadily and quickly.

        Slip compensation

        It is to compensate the slip deviation caused by increased load.

        Hopping frequency

        It is to prevent the resonance with load.

        Dropping function

        It is to balance the several motors with the same load.

        Timing control

        The frequency inverter may stop working after the given time.

        Technical specification of E-Series Frequency inverter

         

        Item

        Specification

        Functions of enhanced type

        Built-in virtual delay timer

        It may conduct simple logic programming for multi-functional output terminals and digital input terminals; therefore, it may be considered as equivalent to the digital input terminal and may realize output via multi-functional output terminal.

        Built-in timer

        It has 2 built-in timers to collect input timing signals and then output the signals.

        Those timers may be used together or independently.

        Built-in operation module

        It has 1 quad operation module and may conduct simple addition, subtraction, multiplication, division, judgment of size and integral operations.

        Communication

        E100

        The control panel has RS 485 communication interface and it supports MODBUS protocol.

        E102/E180

        The control panel has no RS communication interface and shall be installed with an external communication expansion card.

        It supports standard MODBUS protocol and may be installed with MODBUS communication expansion card.

        Encoder

        E100

        It may connect to the encoder via DI5 and DI6 terminals on the control panel. Such connection may realize SVC easily via PID control and may be applied to those requiring lower control precision.

        E180

        Since the control panel has no encoder interface, it shall be installed with an expansion card. It supports ABZ incremental encoder, UVW incremental encoder and rotary transformers. Such connection may realize high performance VC and may be applied for those requiring higher control precision.

        Type of motor

        E100/E102

        It can only drive the asynchronous motor

        E180

        It may drive the asynchronous motor and the synchronous motor.

        Display

        Operation information

        Given frequency, output frequency, output voltage, bus voltage, input signal, feedback value, modular temperature, output frequency, synchronous speed of motor. It may show 32 information by use of >> key.

        Error information

        It may save the 3 failure information with frequency, current, bus voltage, output/input terminal status when failed under failure protection status.

        Protection

        Frequency inverter protection

        It may protect the equipment against over current, over voltage, modular failure, under voltage, over heat, over load, external failure, EEPROM failure protection, grounding protecting and default phase.

        Alarm of frequency inverter

        It may protect the equipment and send over-load alarm

        Instant power down

        It may keep running in the case of lower than 15 ms.

        It may be restarted automatically in the case of larger than 15 ms.

        Environment

        Ambient temperature

        -10~40

        Storage temperature

        -10~40

        Ambient humidity

        90% RH maximally, non-condensing

        Height/vibration

        Lower than 1000m, 0.6g

        Place of application

        No etchant gas, inflammable gas, oil mist or dust.

        Cooling method

        Forced cooling

        E Series Inverter Model and Capacity Table

         

        Series No.

        Model

        Rated Capacity

        (kVA)

        Rated Input Current

        (A)

        Rated Output Current

        (A)

        Adaptive Motor

        (kW)

        Brake Unit

        DC Reactor

        LCD Keyboard

        E100/E102 Series

        S2 (Single-phase220V, 50/60Hz)

        CDI-E100G0R4S2B

        0.8

        5.0

        2.0

        0.4

        Standard Built-in

        N/A

        N/A

        CDI-E100G0R75S2B

        1.5

        9

        4.0

        0.75

        CDI-E100G1R5S2B

        2.7

        15.7

        7.0

        1.5

        CDI-E100G2R2S2B

        3.8

        27

        10.0

        2.2

        T2 (Three-phase 220V, 50/60Hz)

        CDI-E100G0R4T2B

        0.8

        2.3

        2.0

        0.4

        Standard Built-in

        N/A

        N/A

        CDI-E100G0R75T2B

        1.5

        6

        4.0

        0.75

        CDI-E100G1R5T2B

        2.7

        8.8

        7.0

        1.5

        CDI-E100G2R2T2B

        3.8

        12.5

        10.0

        2.2

        T4 (Three-phase 380V, 50/60Hz)

        CDI-E100G0R75T4B

        1.5

        3.4

        2.3

        0.75

        Standard Built-in

        N/A

        N/A

        CDI-E100G1R5T4B

        3.0

        5.0

        3.7

        1.5

        CDI-E100G2R2T4B

        4.0

        5.8

        5.1

        2.2

        CDI-E100G3R7T4B

        5.9

        10.5

        8.8

        3.7

        E180 Series

        T4 (Three-phase 380V, 50/60Hz)

        CDI-E180G0R75T4B

        1.5

        3.4

        2.3

        0.75

        Standard Built-in

        N/A

        Optional

        CDI-E180G1R5T4B

        3

        5.0

        3.7

        1.5

        CDI-E180G2R2T4B

        4

        5.8

        5.0

        2.2

        CDI-E180G3R7/P5R5T4B

        5.9/8.5

        10.5/15.5

        8.8/13

        3.7/5.5

        CDI-E180G5R5MT4B

        8.5

        15.5

        13

        5.5

        CDI-E180G5R5/P7R5T4B

        8.5/11

        15.5/20.5

        13/17

        5.5/7.5

        CDI-E180G7R5/P011T4B

        11/17

        20.5/26

        17/25

        7.5/11

        CDI-E180G011MT4B

        17

        26

        25

        11

        CDI-E180G011/P015T4BL

        17/21

        26/35

        25/32

        11/15

        Standard Built-in

        CDI-E180G015/P018.5T4BL

        21/24

        35/38.5

        32/37

        15/18.5

        CDI-E180G018.5/P022T4

        24/30

        38.5/46.5

        37/45

        18.5/22

        Optional Built-in

        Optional Built-in

        CDI-E180G022/P030T4

        30/40

        46.5/62

        45/60

        22/30

        CDI-E180G030/P037T4

        40/50

        62/76

        60/75

        30/37

        CDI-E180G037/P045T4

        50/60

        76/92

        75/90

        37/45

        Optional Built-out

        CDI-E180G045/P055T4

        60/72

        92/113

        90/110

        45/55

        CDI-E180G055/P075T4

        72/100

        113/157

        110/152

        55/75

        CDI-E180G075/P093T4

        100/116

        157/180

        152/176

        75/93

        Optional Built-out

        CDI-E180G093/P110T4

        116/138

        180/214

        167/210

        93/110

        CDI-E180G110/P132T4

        138/167

        214/256

        210/253

        110/132

        CDI-E180G132/P160T4

        167/200

        256/305

        253/300

        132/160

        CDI-E180G160/P185T4

        200/224

        305/344

        300/340

        160/185

        CDI-E180G185/P200T4

        224/250

        344/383

        340/380

        185/200

        CDI-E180G200/P220T4

        250/276

        383/425

        380/420

        200/220

        Standard Built-in

        CDI-E180G220/P250T4

        276/316

        425/484

        420/480

        220/250

        CDI-E180G250/P280T4

        316/355

        484/543

        480/540

        250/280

        CDI-E180G280/P315T4

        355/395

        543/605

        540/600

        280/315

        CDI-E180G315/P355T4

        395/447

        605/683

        600/680

        315/355

        CDI-E180G355/P375T4

        447/467

        683/714

        680/710

        355/375

        CDI-E180G375/P400T4

        467/494

        714/753

        710/750

        375/400

        CDI-E180G400/P500T4

        494/612

        753/934

        750/930

        400/500

        CDI-E180G500/P630T4

        612/790

        934/1206

        930/1200

        500/630

        CDI-E180G630T4

        790

        1206

        1200

        630

        Model selection table of DELIXI frequency inverter (- indicates having no such function indicates supporting such function)

         

        Item

        Specification

        9100S Series

        Scope of power

        Single phase 220V

        0.4~2.2kW

        --

        Three phase 380V

        --

        Input configuration

        Digital input

        6

        Analog input

        2

        Output configuration

        Relay output

        1

        Open collector output

        --

        Analog output

        1

        Pulse output

        --

        Keyboard

        LED nixie tube

        LCD screen with Chinese characters

        --

        Built-in brake unit

        --

        Control power

        P24V

        --

        Type of motor

        Asynchronous motor

        Synchronous motor

        --

        Type of control

        V/F control

        SVC

        --

        VC

        --

        Operation mode

        Speed mode

        Torque mode

        --

        Communication

        RS485

        --

        Main functions

        Rapid current limiting

        --

        Built-in analog relay

        --

        Built-in timer

        --

        Built-in operation modular

        --

        Background software

        --

        Speed tracking

        --

        Parameter identification

        --

        AVR function

        --

        Parameter backup

        --

        Dropping control

        --

        Protection

        Over current, over voltage

        Output grounding

        --

        Input/output default phase

        --

        Motor overload

        --

         

        Main products

        E102 Series

        E100 Series

        E180 Series

        0.4~2.2kW

        0.4~2.2kW

        --

        0.4~2.2kW

        0.4~2.2kW

        --

        0.75~3.7kW

        0.75~3.7kW

        0.75~75kW

        5 (1 for high-speed input, only internal power sink type connection is allowed)

        6 (1 for high-speed input, external power source type and sink type connections are allowed)

        6 (1 for high-speed input, external power source type and sink type connections are allowed) (4 expandable)

        2

        2

        2 (1 expandable)

        1

        2

        2

        --

        1

        1, 2 expandable

        1

        2

        2

        --

        1

        1

        --

        --

        15kW or lower (18.5 ~30kW optional)

        (without current-limiting protection)

        (without current-limiting protection)

        (without current-limiting protection)

        --

        --

        --

        --

        (with communication expansion card)

        (with communication expansion card)

         You are here : Home > Products > Freuency Inverter